대한전기학회논문지 (The Transactions of the Korean Institute of Electrical Engineers)
- 제43권2호
- /
- Pages.278-285
- /
- 1994
- /
- 0254-4172(pISSN)
부하반환법에 의한 20KVA 비정질 변압기의 경년열화 연구
Aging Test of 20kVA Amorphous Core Transformer by Loading Back Method
초록
Aging test was done by loading back method for 20kVA amorphous core transformers manufactured by Hyosung Industries Co. and korea Electric Power Corporation. Iron losses, copper losses and insulation oil temperatures of the transfromers was measured for all the testing period. Expected life of amorphous core transformers on the basis of the degradation of the insulators was 46 years at 100% load, and 2.4 years at 130% load. Average temperature rising of transformer oil of amorphous core transformers was higher than that of silicon steel core transformers. Hence lowering the oil temperature by optimized design is needed for improving the expected life of the amorphous transformers.
키워드