Simulation of Pipe Network for Optimum Heat Supply in the Hot Water Heating System of Apartment House

공동주택 온수난방 시스템의 적정 열공급을 위한 배관망 시뮬레이션

  • 김주용 (고려대 대학원 기계공학과) ;
  • 민만기 (고려대학교 기계공학과) ;
  • 최영돈 (고려대학교 기계공학과)
  • Published : 1993.08.01

Abstract

Pipe network of hot water heat supply system in an apartment house was analyzed. Flowrate and supply heat capacity of each household in which constant flowrate balancing valve is installed in a single zone system were calculated and the results were investigated. In the existing piping system, the non-uniformity of heat supply with floors due to the static pressure and temperature difference between supply main and return main can not be avoided and this tendency get intense with the increase of the height of building. The non-uniformity of heat supply can be prevented by the installation of balancing valve at each household, however if the performance of supply pump is not sufficient to overcome the energy loss due to the installation of balancing valve for constant flow rate or if the selection of the valve capacity is not adequate, the valves will may lose their controllability.

Keywords