Seismic Qualification of Class 1E Battery by Combined Analysis and Testing

수치해석과 실험을 통한 안전등급 축전지의 내진검증

  • 김영중 (한국해사기술연구소, 진동연구실) ;
  • 박성환 (한국해사기술연구소, 구조연구실) ;
  • 정태영 (한국해사기술연구소, 진동연구실) ;
  • 정정훈 (한국해사기술연구소, 진동연구실)
  • Published : 1993.03.01

Abstract

The seismic qualification for the class 1E battery of Korea Multipurpose Research Reactor was accomplished by the analysis as well as testing. The full rack consists of 4 similar sections of typical frame structure and contains 60 cells. However, since the seismic qualification was required on the frame structure and only on 3 aged ones among 60 dells, 2 sections of the full rack were assembled as a test rack with 28 cells including the 3 aged cells for an economic test. Seismic analysis for the full rack was carried out using the finite element program ANSYS. The modal parameters identified from the resonance search thest on the test rack were used to the seismic analysis of the full rack. It was confirmed that the test rack could represent the full rack with regards to seismic responses and function of cells, and that the full rack and aged cells were qualified to the given seismic test requirements.

Keywords

References

  1. 한국소음진동공학회지 v.1 no.1 6자유도 진동대-특성 및 활용방안 이호섭
  2. IEEE std. 344 IEEE Recommended Practices for Seismic Qualification of Class 1E Equipment for Nuclear Power Generating Stations
  3. IEEE Transactions on Power Apparatus and System v.PAS-101 no.9 Class 1E Seismic Qualification by Test and Analysis of Generic Multi-Cabinet Electrical Equipment Fischer,E.G.;Sucevic,J.M.;Fischer,T.P.
  4. KRISO Report No. BSI935-1628E.D. Seismic Qualification Test on the Class 1E Barrery for KMRR Kim,Y.J.(et al.)
  5. ANSYS Revision 4.4 Swanson Analysis Systems
  6. Modal Testing: Theory and Practice Ewins,D.J.
  7. GYB-551-KMT-001 Equipment Qualification Program for Class 1E Battery of KMRR
  8. Regulatory Guide 1.61 Damping Values for Seismic Design of Nuclear Power Plants