간접냉각이 이용된 지중송전케이블의 적정냉각조건에 관한 연구

A Study on the Optimum Cooling Condition of the Underground Power Transmission Cable Equipped with a Separate Pipe Cooling System

  • 박만흥 (한국전력기술(주) 전력기술개발연구소) ;
  • 최규식 (한국전력기술(주) 전력기술개발연구소) ;
  • 서정윤 (한국전력공사 기술연구원) ;
  • 김재근 (한양대학교 대학원) ;
  • 이재헌 (한양대학교 기계공학과)
  • 발행 : 1992.11.01

초록

The transmission current in a power cable is determined under the condition of separate pipe cooling. To this end, the thermal analysis is conducted with the standard condition of separate pipe cooling system, which constitutes one of the underground power transmission system. The changes of transmission current in a power cable with respect to the variation of temperatures and flow rates of inlet cooling water as well as the cooling spans are also determined. As a consequnce, the corresponding transmission current is shown to vary within allowable limit, resulting in the linear variation of the current for most of the cable routes. The abrupt changes of current, however, for the given flow rate of inlet cooling water in some cooling span lead to the adverse effects on the smooth current transmission within the underground power transmission system. In practice, it is expected that the desinging of the separate pipe cooling system in conjunction with the evaluation of system capacity should take into account the effects of design condition on the inlet cooling flow rate.