Acknowledgement
Supported by : 한국과학재단
The aim of this study was to develop a phytotron for studying the effects of environmental factors such as temperature and humidity on plant growth. This equipment consists of the growth chamber, and the measurement and control system including control algorithms required for optimum operation. As the first step of the study, a temperature and humidity control system was developed. The results of this study are summarized as follows ; 1. Pt-100 was selected to measure temperature and a linearized op-amp circuit was developed for signal conditioning. 2. Pt-100 wet bulb thermometer based on Asmann's principle was developed to measure relative humidity. 3. Temperature and relative humidity conditions were controlled by ON-OFF and PWM operation using a PID controller. And an autotuning algorithm using the characteristics of step response was developed to determine optimal PID constants which were independent of the size of apparatus and environmental factors. 4. Under the ambient temperature of
Supported by : 한국과학재단