The Transactions of the Korean Institute of Electrical Engineers (대한전기학회논문지)
- Volume 41 Issue 5
- /
- Pages.445-458
- /
- 1992
- /
- 0254-4172(pISSN)
A Study on the Variation of the Transmission Capacity by External water Cooled System with Trough in Tunnel
전력구트라프내간접수냉방식에서의 송전용량 변화에 관한 연구
Abstract
As one of the forced cooling method of the underground power transmission system, external water cooled system with trough in tunnel was investigated. This study is performed on thermal analysis for a standard condition to determine the cable transmission current of the underground power transmission system about the cooling facility. A parametric study was performed for the inlet water temperatures, flow rates, the inlet air velocities, flow rates and the cooling spans. This study shows that the cable transmission current varies within the allowable limitation in compliance with the variation of inlet water temperatures and flow rates. It exhibits little variations for the most intervals in compliance with the variation of inlet air temperatures and flows. But, the cable transmission current fast reduces for a specified interval and consequently affects the underground transmission system. As a result, when the actual forced cooling system is designed, the design conditions of inlet air have to be considered as the most important parameters in determination of the cable transmission current.
Keywords