Cold Air/Water Distribution System with Ice Storage

빙축열을 이용한 저온급기/급수 냉방 시스템

  • 김경훈 (대우캐리어(주) 마케팅부) ;
  • 이종원 (대우캐리어(주) 기술연구소)
  • Published : 1991.04.01

Abstract

This paper presents some design guidelines for using cold air/water distribution to cool commercial and industrial buildings. Cold air /water distribution systems provide primary air/water for space conditioning at nominal temperature between $3^{\circ}C$ and $10^{\circ}C$ ($4{\sim}5^{\circ}C$ might be recommendable for better selection). By using lower temperature primary air/water equipment could be downsized, means lower first costs, and often reduce annual energy costs up to 50% less than that of the conventional ($13^{\circ}C$) system. This concept takes full advantages of the $2{\sim}4^{\circ}C$ chilled water (brine) available with ice storate systems.

Keywords