A Study on the Measurements of Discharge Parameters in Case of the Switching Impulse Breakdown of a Large Air Spacing

이격거리가 큰 전국의 공기절연파괴 현상시 발생하는 인자측정에 관한 연구

  • Published : 1991.12.01

Abstract

The paper presents the measurement results on the parameters affecting the breakdown mechanism of a large air spacing under switching impulse voltages. Measured parameters are the velocities of leader channels, predischarge currents, electric charges injected into the rod-plane air gap and electric field intensities on the plane. For the 3m air gap under switching impulse voltages, the velocities of leader channel have been measured to be of 1cm/x10S0-6Ts - 5cm/x10S0-6Ts, electric field intensity of 2kv/cm, predischarge current of 1.2-1.6A, the charges injected into the air gap of 11-40x10S0-6TC for 400-887kV impulse voltages.