Effects of Fin Configuration on the Evaporator Performance

휜 형상에 따른 증발기의 전열 성능

  • Published : 1990.02.01

Abstract

An experimental investigation was made to study the performance characteristics of evaporator having different fin configurations and tube inner grooves. Three different types of fin such as super slitted fin, slitted fin, plain fin, and two types of tube such as inner grooved tube, and bare tube, are tested varying the air velocity, evaporation temperature and superheat of refrigerant. Results show that in the range of air side Reynolds number $3{\times}10^3\;-\;1.5{\times}10^4$ evaporator with super slitted fin and inner grooved tube shows best performance. It is 80% higher in overall heat transfer coefficient and 2.6 times higher in pressure loss compared to that with plain fin inner grooved tube. Friction factor is found to be almost independent of evaporating temperature and degree of superheat, while Colburn j factor varies with evaporating temperature.

Keywords