Cooling Performance on the Small Diesel Engine

소형(小型)디젤기관(機關)의 냉각성능(冷却性能)에 관(關)한 연구(硏究)

  • Kim, Sung Rai (Dept. of Agricultural Machinery Engineering, Coll. of Agriculture, Chungnam Nat'l Univ.) ;
  • Myung, Byung Soo (Dept. of Agricultural Machinery Engineering, Coll. of Agriculture, Chungnam Nat'l Univ.)
  • 김성래 (충남대학교 농과대학 농업기계공학과) ;
  • 명병수 (충남대학교 농과대학 농업기계공학과)
  • Published : 1990.06.30

Abstract

This study was conducted to obtain basic data for the design of cooling system by the test of engine performance of the power tiller being used widely in the rural area. Among the various factors affecting engine performance, the flow rate of cooling water was considered as the major factor in this study. Motoring loss, output, fuel consumption ratio, torque, heat absorption of cooling water, and thermal efficiency were measured and analyzed based on three flow rates of cooling water such as 15, 20, and $25{\ell}/min$. The results obtained were as follows : 1. Motoring loss of the engine was 1.371 kW at 2,200 rpm., and mechanical efficiency was 79.1% at rated output level. 2. Output power of the engine increased with the flow rate of cooling water increased. 3. BSFC was 282.9g/kW-h at the flow rate of $20{\ell}/min$, and the temperature of cooling water at outlet was $80.9^{\circ}C$. 4. There was a little variation of torque of the engine depending on the flow rate of cooling water. 5. Absorption of heat by cooling water was increased with the increase of flow rate. 6. The highest thermal efficiency of 32.3% at the flow rate of $20{\ell}/min$ was observed.

본(本) 실험(實驗)은 동력경운기(動力耕耘機)에 탑재(搭載)되는 소형(小型)디젤기관(機關)의 냉각수(冷却水)의 적정량을 구명(究明)하기 위한 기초적(基礎的)인 실험(實驗)으로 냉각수(冷却水) 순환량(循環量) 15, 20, $25{\ell}/min$의 3수준(水準)으로, 변화(變化)시켰을 때의 기계손실(機械損失), 출력(出力), 연료소비율(燃料消費率), 토크, 냉각수흡열양(冷却水吸熱量), 열효율등(熱效率等)에 미치는 영향(影響)을 측정(測定) 분석(分析)한 결과(結果)는 다음과 같다. 1. 공시기(公試機)의 Motoring loss는 상용회전(常用回轉) 2,200rpm에서 1.371kW로 정격출력시(定格出力時)의 기계효율(機械效率)은 79.13%로 외국제품(外國製品)보다 약간(若干) 낮았다. 2. 냉각수(冷却水) 순환량(循環量)을 증가(增加)시킴에 따라 출력(出力)은 증가(增加)되는 경향(傾向)을 보였다. 3. 정격출력시(定格出力時) 연료소비율(燃料消費率)은 냉각수순환량(冷却水循環量) $20{\ell}/min$일때 282.93g/kW-h로서 가장 작게 나타났으며 이때 냉각수(冷却水)의 출구온도(出口溫度)는 $80.9^{\circ}C$이었다. 4. 냉각수(冷却水) 순환량(循環量)의 변화(變化)에 따른 토크의 변화(變化)는 거의 없었다. 5. 기관(機關)의 냉각수(冷却水) 흡열량(吸熱量)은 냉각수(冷却水) 순환량(循環量)의 증가(增加)에 따라 증가(增加)하는 경향(傾向)을 나타내었다. 6. 열효율(熱效率)은 냉각수(冷却水) 순환량(循環量) $20{\ell}/min$에서 32.31%로 가장 높게 나타났다.

Keywords