Journal of the Korean Institute of Telematics and Electronics (대한전자공학회논문지)
- Volume 27 Issue 1
- /
- Pages.10-19
- /
- 1990
- /
- 1016-135X(pISSN)
A Case Study on Application of Fault Tolerant Control System to Boiler Controller in Power Plant
발전소 보일러 제어기에 대한 내고장성 제어 시스템의 적용에 관한 연구
- ;
- ;
- ;
- Zeung Nam Bien
- Published : 1990.01.01
Abstract
A fault tolerant control system, in which a digital back-up controller system is added on the existing analog control system, is developed for enhancing reliability of boiler control system in power plant. The digital back-up controller system(DBCS) has a multi-processor structure with capabilities of fault diagnosis, back-up control, self test, and graphic monitoring. Specifically, switching mechanism composed of expandable modules is designed so that back-up controller takes over any faulty control loops and the number of back-up control loops is determined as that of simultaneous faults. A process simulator that simulates the boiler analog control system is developed for safety test and performance evaluation prior to real plant application. DBCS is installed at the Ulsan thermal power plant, and fault tolerant control performance is assured under the faults that some controller modules are pulled out.
Keywords