히이트파이프 다발을 이용한 냉축열시스템에서의 대류열전달에 관한 연구

A Study on the Convective Heat Transfer in a Regenerative Ice Energy System by a Bundle of the Heat-pipes.

  • 발행 : 1990.08.01

초록

In the design of an electric power plant, the capacity to meet the peak load demand is one of the important factors to be considered. This peak load usually occurs when the most of the cooling air conditioning systems are being operated during daytime in summer season, which inevitably entails the construction of an additional electric power plant. This study is aimed to carry out a basic experiment for the development of a cooling air conditioning system using the ice energy by the surplus electric power during the night-time. The experimental apparatus consists of four major parts; (1) the heating section consisting of the air duct and I.D. fan, (2) the cold section with the ice chamber, (3) the bundle of heat pipes made in a form of the staggered arrangement with ${C_y}/{d_o}$=2.0 and ${C_x}/{d_o}$=1.73, (4) the refrigerator system to cool down the ice chamber. This study involves an intensive experiment concerning the convective heat transfer of the air flow surrounding the bundle of heat pipes. This major experimental parameters are the amount of working fluid, the velocity of air and the working temperature. The major findings of the present study are as follows; (1) The optimum amount of the working fluid necessary for the horizontal heat pipes is much more than that for the vertical type. (2) The convective heat transfer coefficients of the air are coincided with the empirical equations of Grimson and ${\breve{Z}ukauskas}$. (3) The equation of the mean heat transfer coefficient obtained in the present study is ${N_um}=0.32 {Re_max^{0.63}}$.

키워드