Study on the Unsteady Contaminated Particle Transportation in the Flow Field for the Super Clean Room

초청정 클린룸 난류유동장내에서의 오염입자 비정상 전파거동에 관한 연구

  • Published : 1990.03.01

Abstract

Steady state turbulent airflow and unsteady characteristics of generation, transportation, and recovery behavior of contaminate particles in the simplified 2 dimensional Vertical Laminar Flow (VLF) type clean room was numerically simulated using the low Reynolds number k-over bar.epsilon- turbulent model. Characteristics of airflow in VLF type clean room are greatly affected by the recirculation zone around working surface. The recirculation zone must be considered at the time of clean room design because the recirculation zone whose area increases with increment of inlet velocity exerts bad influence upon the performance of clean room in terms of particle contamination. The location of maximum particle concentration changes from the location of particle source to the recirculation zone, while averaged particle concentration is reduced exponentially with time. Recovery time of clean room with spontaneous particle generation source is inversely proportional to inlet velocity. We introduce nondimensionalized recovery time through the dimensional analysis, which can indicates the general performance of clean room with design structure change. It was identified that .tau. is independent of inlet velocity and background concentration. Therefore .tau. can be the simple factor to compare the different structure of clean room in terms of dynamic response to contamination and becomes larger with better structure of clean room.

Keywords