과제정보
연구 과제 주관 기관 : 한국과학재단
The ASHRAE Simplified Energy Analysis Procedure using the Modified Bin Method(SEAP) is compared with the hourly calculation program, HASP/ACLD. The HASP/ACLD model office building with VAV system in Seoul is used as the basis for comparison. And the parameters considered are glass to wall area ratio and internal heat gains. The results show that SEAP predictions of annual energy use agree with HASP/ACLD predictions within 5% deviation. But there is a large difference in cooling and heating energy as glass to wall area ratio is varied. The SEAP cooling energy is 65-85% and the heating energy is 104-160% of the HASP/ACLD results. This is probably due to the solar heat gain data. the data related to the SEAP must be developed prior to use it.
연구 과제 주관 기관 : 한국과학재단