An Experimental Study on the Performance of Heat Pump Air Conditioner according to Frequency Modulator for Cooling and Heating

주파수변조장치를 이용한 열펌프식 공기조화기의 냉방-난방에 관한 실험적 연구

  • 이대우 (한양대학교 대학원 기계공학과) ;
  • 조진호 (한양대학교 공과대학 기계공학과)
  • Published : 1989.08.01

Abstract

This paper is an experimental study on the pleasantly suitable cool/warm air conditioning system in order to minimize the energy consumption by attaching the electronic-controlled device to the heat pump air conditioning system.While the cool/warm air conditioning, the air temperatures in the entrance and exit of the indoor heat exchangers should be checked and when the surface of heat exchanger is reached to the dew point temperature, a speed of the compressor is to be automatically controlled by anti-dewing system in order to minimize the energy consumption.At the result of this study, the energy consuming amount is saved about 5% more than that of the conventional air conditioning system by prevent unnecessary dew forming.