An Analysis on Removal Effect of Biological Contaminants in the Process of Municipal Sewage Treatment System - On the Seoul Cheonggye Cheon Sewage Treatment Plant

도시하수 처리에 의한 미생물 오염의 제거효과에 관한 조사연구(I) -청계천 하수처리장을 중심으로-

  • Yu Byong Tae (Seoul Metropolitan Government Institute of Health and Environment) ;
  • Chung Yong (Graduate School of Health Scienceand Management, Yonsei University)
  • 유병태 (서울시 보건환경연구소) ;
  • 정용 (연세대학교 보건대학원)
  • Published : 1988.05.01

Abstract

This investigation was carried out to evaluate the removal effect of biological contaminants for the municipal sewage treatment process at Cheonggye Cheon terminal plant which in the first plant for municipal sewage treatment in Seoul area. It was conducted in raw influent, primary treatment water and secondary treatment water from September, 1986 to July, 1987. The results were as follow; 1, The primary treatment could eliminate microbials for $65.38\%$ of total bacteria, $64.35\%$ of total coliform, $62.16\%$ of fecal coliform $69.48\%$ of pseudomonas and $64.70\%$ of fecal streptococci in averages for a year respectively. 2. The secondary treatment could eliminate microbials for $97.50\%$ of total bacteria, $97.30\%$of total coliform, $95.95\%$ of fecal coliform, $97.00\%$ of pseudomonas and $96.53\%$ of fecal streptococci in average for a year respectively. 3. In the detect rate of pathogenic agent, salmonella spp was decreased $12.5\%$ to $4.2\%$ in primary treatment and it was not detected in secondary treatment, shigella spp was detected $4.2\%$ in influent water but it was not detected in primary and secondary treatment. 4. In the seasonal variation of treatment effect, the removal of summer was the highest, and the removal of all item in winter was lower than the other seasons. 5. There was significant correlation between water temperature and microbal all items (P<0.05) $NH_3-N$ and Microbal items (P< 0.01) at raw water.

Keywords