A Study on the Optimization of Condenser according to Design Factors in Heat Pump System

열(熱)펌프시스템에서 각종(各種) 설계인자(設計因子)들에 따른 응축기(凝縮器)의 최적설계(最的設計)에 관한 연구(硏究)

  • Published : 1988.08.01

Abstract

This study optimized the condenser dimension of heat pump system with the heat sources which are solar irradiation and ambient air. At first, the author selected the principal design factors influencing the performance of heat pump system. And the author considered the variation of condenser dimension according to the variation of the selected design factors, that is, ambient air temperature, condenser temperature, degree of superheating, degree of sub-cooling and irradiation. As a result this study, among refrigerants R12, R22 and R500, refrigerant R22 has more heating output than R12 and R500, and the coefficient of performance on this heat pump system is not greatly influenced by the degree of superheating and degree of sub cooling. The ambient air temperature is below $5^{\circ}C$ at balance point and the optimal tube length of condenser dimension is about 3.8 m. Also the author gained the optimal design diagram for the optimization of condenser dimension according to various design factors.