A Study on the Improvement of a Cooling System by the Increment of Room Humidity without Reheating Process

실내 습도 증가를 이용한 무재열 냉방시스템 개선에 관한 연구

  • 이홍주 (육군사관학교 병기공학과) ;
  • 김용구 (단국대학교 기계공학과, ㈜한미기술용역(T. A. B.))
  • Published : 1987.12.01

Abstract

In a room air conditioning cooling system, if the room-sensible-heat-factor as plotted on a Psychrometric Chart intersects the saturation curve below the apparatus leaving air dewpoint, reheat must be used to maintain the design room air conditions. However, if the design room humidity is permitted to be raised to some degree, the cooling system will not require reheat as a new room-sensible-heat-factor line is developed between the apparatus leaving air dew-Point and the adjusted design room air conddition point. The advantages to this are the cost of reheat equipment and operation can be avoided. The cycle of this system can be shown on a Psychrometric Chart to plot the design condition points.

Keywords