Transient Analysis of Heat Transfer and Pressure Variation for LPG Tank with Metal Explosion Suppression Material

금속폭발억제재가 충진된 LPG 탱크의 비정상 열전달 및 압력변화 해석

  • 김호영 (고려대학교 공과대학 기계공학과) ;
  • 장효환 (고려대학교 공과대학 기계공학과) ;
  • 전철균 (고려대학교 대학원)
  • Published : 1987.08.01

Abstract

As one of the explosion suppression methods of LPG tank exposed to hot environment by an accident or fire, some material which has large heat capacity and thermal conductivity can be installed inside the LPG tank in order to suppress the temperature increasement of tank wall. In the present study, theoretical model for the horizontally locating cylindrical LPG tank with and without the aluminum explosion suppression material has been developed to predict the characteristics of system. As a parametric study, effects of two major parameters, thickness of material filling and initial vapor volume fraction, on the time variation of wall temperature, temperature and pressure in tank are numerically examined. The results of present study show that the thickness of material filling does not give big differences in the suppression characteristics when the thickness of filling is larger than three inches. In case of material filling, there are marked suppression effects to the increase-ment of wall temperature, average vapor temperature and pressure in tank compared with the case of no filling.

Keywords