The Estimation of Sound Attenuation Caused by Duct Silencer Using Sound Intensity Method

음향인텐시티법을 이용한 공조 덕트소음기의 감음성능평가방법에 관한 연구

  • 김석홍 (漢陽大學敎 大學院 建築工學科) ;
  • 손장열 (漢陽大學敎 建築工學科) ;
  • 오재응 (漢陽大學敎 建築工學科) ;
  • 김여식 (漢陽大學敎 建築${\cdot}$環境工學硏究室)
  • Published : 1987.06.01

Abstract

This paper is to suggest the test method of sound attenuation caused by absorptive duct silencer using sound intensity method in field. In order to estimate sound attenuation, sound power being radiated from sound power source and duct exhaust terminal was measured by the sound pressure method and sound intensity method in semianechoic and common room. The results of the measured sound attenuation values by sound intensity method are more similar to those of theoretical calculation than those by the sound pressure method. In addition, sound intensity method is much less influenced by sound field condition or continuous background noise than the sound pressure method.

실험실이 아닌 일반음장에서 음향인텐시티법을 이용하여 공조덕트 소기기의 감음성능 평가방법을 검토하였다. 음향인델시티법에 의한 감음량 측정치는 음압법에 의한 측정치보다 이논치와 비교적 잘 일치하였으며, 음향인텐시티법은 음압법에 비하여 음장조건에 따른 영향을 비교적 적게 받는 것으로 나타났다.

Keywords