The Inprovement of the Heat Exchanger Performance by Shape Modification(I)-Experimental Analysis of the Heat Transfer Enhancement by Attached Wires in a Double Pipe Heat Exchanger-

형상변화 에 의한 열교환기 의 열전달 성능 향상 (I) -이중 동심원관내에 와이어 부착시의 열전달 촉진에 대한 실험적 해석-

  • 노승탁 (서울대학교 공대 기계공학과) ;
  • 이택식 (서울대학교 공대 기계공학과) ;
  • 강신형 (서울대학교 공대 기계공학과) ;
  • 김진오 (서울대학교 대학원 기계공학과)
  • Published : 1985.01.01

Abstract

The various sizes of wires are attached to the outside of the inner tube in a double pipe heat exchanger to enhance the thermal performance. The diameters of the wires range from 0.5mm to 1.6mm while the pitches are chosen between 5mm and 50mm. Experiments have been performed with the range of Reynolds numbers from 15000 to 30000 in annular space where air flows. The friction factors are increased by 1.5 to 4.5 times depending on the sizes and the pitches of the wires. However, the Nusselt numbers are increased by the factors of 1.8 to 2.8 within this experimental range. It is suggested that there should be an optimum configuration rendered when the weighting values of the heat transfer promotion and the pumping power are given.

본 연구에서는 이중관 열교환기의 내관의 바깥 벽면에 반지 형태의 원형돌기 를 부착하여 굵기와 피치를 변화시키면서 압력손실과 열전달계수의 변화를 실험적으로 고찰하였다.