Characteristics of Transient Overvoltages for the Towers with Time Varying Tower Footing Resistance

  • 발행 : 1984.03.01

초록

This paper investigated the characteristics of transient overvoltages on the tower caused by time varying tower footing resistance in the path of lightning stroke current entering earth on transmission lines. The tower with time varying tower footing resistance was simulated and the transient overvoltageson the tower due to lightning stroke current were computer by Nodal Solution Method. From the results, it was found that the determination of the steady state values as a limit of inductive tower footing resistance causes higher transient overvoltages than CFO voltages of insulator strings and V-T characteristics of the insulator strings should be considered for computation of backflashover rate.

키워드