Cyclic performance of residential air-to-air unitary heat pump

주택용 열펌프의 단속운전성능

  • 민만기 (고려대학교 공과대학 기계공학과)
  • Published : 1983.12.01

Abstract

Cyclic heating performance of 3 ton air-to-air unitary heat pump installed in a residence in the Washington, D.C. area was determined by applying the bin method to field test result. Cyclic degradation coefficient Cn of heat pump may be expressed in terms of heating load factor HLF as the following : $$C_D=\frac{1-HLF^m}{1-HLF}$$ where $$C_D{\ge}m$$ The less is the value of exponent m, the better is, the performance of a heat pump, depending upon the heat pump design.