A Study on Optimum Design Condition for 'HEAT PUMP' System in Korea
한국에 있어서의 히이트 펌프계의 최적 설계 조건에 관한 연구
Abstract
This paper presents, the result of the study for the fluctuant temperature of the out-side air adopting the heat pump system in seoul, Taejean, Taegu, Busan and Jejeu among principle cities in korea for the purpose of checking the heating capacity, Heat pump capacity (outlet capacity), Coefficient of performance and running cost in comparison with the supporting the energy for the boiler's operation. According to the supply temperature changes of the out door coil by the out side air-return air mixing ratio, the Coefficient of performance is increased from 3. 1 to 5.0. Particularly, in Taegu, it is necessary to adopt the heat pump system against the supplement heat supply on the full outside air intake in January of the heating period, and it was recognized that the running cost is cheaper than that of the Boiler use. At the same time, if it is able to get