A study on effect of additives upon A.C. partial discharge in insulating oil

절연유의 교류부분방전에 미치는 첨가물의 영향에 관한 연구

  • Published : 1980.08.01

Abstract

Effect of Argon and Sulfur hexafloride in the transformer oil are experimented under non-uniform A.C. electric field. The result has shown that the corona frequency and corona charge quantity in liquid dielectrics were varied with gas condition in the oil and affected by the additives. SF$_{6}$ that has the effects of pressure and electrical negative characteristic is the most effective. The corona is considered to be the breakdown of bubble produced by gas contained in the oil or by dissociated ion of the oil molecules.s.

Keywords