송전선의 강제재폐로

Forced reclosing in transmission line

  • 발행 : 1980.06.01

초록

This paper deals with the implementation of forced reclosing the transmission line. Because the ground circuit breaker method decrease the secondary arc current sufficiently, the reclosing time can be reduced. As the secondary arc current is large and its residual time is long in UHV transmission line, this method is more effective in that system. The resistance of ground circuit breaker which minimize the secondary arc current is determined according to the system voltage and the length of transmission line.