Lightning protection in an 154kV GIS connected by oil-filled cables

O.F. Cable에 연결된 154kV GIS의 뇌보호

  • Published : 1980.05.01

Abstract

It has been appeared and widely used today SF6 Gas Insulated Substation(Hereafter called GIS) for the power supply to the densely populated area due to the superior insulation withstand ability of SF6 Gas. And to maximize the compact effect of this substation, it is normal practice to connect underground cables. If it is possible to elieminate the redundant lightning arresters using the physical characterestics of travelling waves in underground cables, economical advantages can be obtained together with easy maintenances. It is presented in this paper the possiblity of eliminating the transformer protection lightning arresters under some conditions for the 154kV GIS's (BIL:750kV) which Korea Electric Co. plans to construct using the general purpose digital computer program.

Keywords