Studies on Preventive Methods Against Concrete Corrosion by Sea Water (ll)

조수에 의한 콘크리트 침식방지법에 관한 연구(ll)

  • Published : 1973.06.01

Abstract

This study was carried out to investigate the effects of various mix designs of concrete on the compressive strengths and corrosive rates when the concretes were immersed in sea water of the West Sea, as the part of study related to durated to durability of concrete by action of the sea water. Concrete mix designs used in this study were ordinary Concrete mix, Concrete mixes with different admixtures such as fly ash, pozzolith and vinsol resin, and pozzolan concrete mix. The concrete specimens were made and cured for 7 days and 28 days in the fresh water in accordance with the Korean Standard specification for concrete. Compressive strengths of the specimens were measured after immersing the specimens for one year in fresh water and sea water which were placed indoors. The sea water used in this test was taken from the Bay of Ahsan. Corrosive rate was also tested after immersing the specimens in the same sea water and placed indoors for one year. The results obtained from the tests are summarized as follows; 1. Compressive strength of an ordinary concrete was the lowest of the various mix desings of concrete immersed both in the fresh water and the sea water. Therefore, the uses of pozzolan cement, fly ash, pozoolith and vinsol resin in mix design of concrete had and effect on increasing compressive strength. 2. Pozzolan concrete was the most effective on compressive strength in the fresh water, but it had less effect than concrete with fly ash admixture immersed in the sea water. 3. The use of fly ash admixture in mix design of concrete showed higher strength as the immersing age is longer both in fresh water and sea water than the other concretes besides pozzolan concrete, but the concretewith fly ash admixture had lower strength than pozzolan concrete in the sea water. Therefore, concrete with fly ash admixture might be better than the pozzolan concrete as far as durability of concrete to sea water was concerned. 4. The use of pozzolith admixture in mix design of concrete had less compressive strength than the use of pozzolan cement for fly ash admixture both in fresh water and sea water. However, the concrete with pozzolith admixture was much stronger than one with vinsol resin admixture in fresh water, but somewhat stronger in the sea water. 5. Though the use of vinsol resin admixture was more effective than ordinary concrete on compressive strength both in fresh water and sea water, it was the least compressive strength among the other concretes. 6. Relation between compressive strengths and absorption rates of every kind of concrete besides concrete with fly ash admixture showed a linear regression line and the compressive strength is highee as the absorption rate is lower. Concrete with fly ash admixture had extremely high strength in comparison with corresponding adsorption rates of the other concretes. 7. Corrosive appearance on the surface of concretes was not occured significantly when exposed to the sea water for one year, However, the specimens of concretes besides ordinary concrete were a little heavier than those cured in fresh water for 28 days.

이 연구는 해수작용에 대한 콘크리트의 내구성시험의 일환으로 각종 배합설계의 콘크리트에 대하여 1년간 실내에서 해수에 침지하여 압축강도와 부식율을 규명하고저 시도하였다. 각종 콘크리트의 배합설계에 있어서 보통시멘트만을 사용한 것, 혼화제로서 후라이애쉬, 포조리스, 빈솔레진 등을 각각 보통시멘트에 사용한 것, 그리고 포조란 시멘트만을 사용한 것 등으로 구분하고 각 콘크리트 공시체는 K.S 규정에 준하여 만들어 재령 7일 및 28일 양생하였다. 그리고 압축강도시험은 수중과 해수에 각각 1년간 침지한 것에 대하여 강도를 측정하고 부식율시험은 해수중에 1년간 침지한 것에 대하여 부식율을 측정하였다. 이와같은 콘크리트의 압축강도시험과 부식율 시험에 대한 결과를 요약하면 다음과 같다. (1) 압축강도에 있어서 보통콘크리트는 수중이나 해수중에 다 같이 다른 콘크리트의 강도보다 낮으므로 포조란시멘트나 혼화제인 후라이애쉬, 포조리스. 빈솔레진은 각각 그 효과가 인정되었다. (2) 포조란시멘트는 수중에서 강도가 다른 콘크리트보다 가장 높았으나 해수중에서는 후라이애쉬보다 낮은 강도를 나타내었다. 따라서 포조란시멘트는 해수중에서 보다 수중에서 강도상 효과가 있다는 것을 알 수 있다. (3) 후라이애쉬는 수중에서와 해수중에서 다 같이 장기강도에 있어서 높은 강도를 갖인 특성이 있다는 것을 나타내었고, 수중에서는 포조란시멘트에 비하여 강도가 낮었으나 해수중에서는 오히려 포조란 시멘트의 강도를 능가하고 있어 해수중에서는 포조란 시멘트보다 강도상 더욱 그 효과가 크다는 것을 알 수 있다. (4) 포조리스는 후라이애쉬와 포조란시멘트에 비해서 그 효과가 떨어지나 빈솔레진에 비해서는 강도상에 있어서 항상 그 효과가 인정되공 있다. (5) 빈솔레진은 포조란시멘트나 혼화제중에서 강도상 가장 그 효과가 낮으나 보통콘크리트에 비하면 그 효과는 수중이나 해수중에서 다 같이 인정되고 있다. (6) 콘크리트의 압축강와 흡수율과의 관계는 후라이애쉬를 제외하면 다른 재령에서와 같이 흡수율이 적을수록 압축강도는 증가되며 회기직선관계가 성립되었다. 그러나 후라이애쉬는 장기강도에서 그 특징이 현저히 나타나고 있어 다른 콘크리트의 흡수율에 비하여 현저히 높은 강도를 나타내고 있다. (7) 부식율에 있어서는 1년간 해수작용을 받었을 때 각 콘크리트의 유의적인 부식율이 인정될 수 없으며 외관상에서도 부식현상을 식별할 수 없었다.

Keywords