전기의세계
- Volume 22 Issue 3
- /
- Pages.13-24
- /
- 1973
- /
- 1598-4613(pISSN)
Study on Insulation Design of Surge Voltages for Convex Winding type Ribbon Core Transformer
Convex형 권선배치방식을 취한 권철심변압기의 충격파절연설계에 관한 연구
Abstract
In this report, as a method to solve the problems on impulse insulation coordination in ribbon core transformer owing to it's BIL stepping up, new design to alter winding distribution of multiple-layer concentric winding to Convex type winding is proposed. The main focus of this method is to settle the weakness of axial direction insulation strength and as a result of theoretical analysis through experiment of model transformers, the following conclusions are obtained; (a) As the electric loadings in a design which increases by strengthenning axial direction insulation endurance in presently avarilable transformers owing to it's BIL stepping up can be restricted in Convex type winding, reasonable design will be suited to the transformer with higher BIL. (b) Convex type winding is a very improved insulation design in respect of insulation coordination because it has shield plate effect to even impulse oscillation. (c) There is a disadvantage to cause leakage flux to increase in Convex type winding, however, the constancy of electric loadings in a design in spite of BIL stepping up restricts the increase of leakage flux to some extent.
Keywords