This paper presents a robust feedback control design to mitigate the effect of grid voltage disturbances for three-phase grid-connected inverters in distributed generation systems. The proposed strategy consists of two major design steps. First, the controller is synthesized using the internal model principle to achieve a good reference tracking and disturbance rejection performance. Then, the feedback gain is systematically obtained by solving the linear matrix inequality conditions which are directly derived from the stability criteria. The main contribution of this paper is that the complexity of control structure can be substantially reduced and transient response is improved as compared with the existing robust control design methods. The simulation results are given to prove the validity of the proposed control scheme.