Characteristics of Temperature History at Each Section of Mat Foundation Concrete Applying Double Bubble Sheets

이중버블시트를 적용한 매트 기초콘크리트의 부위별 온도이력 특성

  • 김태청 ((주)선엔지니어링종합건축사사무소 건설기술연구소) ;
  • 김종 ((주)선엔지니어링종합건축사사무소 건설기술연구소) ;
  • 전충근 ((주)선엔지니어링종합건축사사무소 건설기술연구소) ;
  • 신동안 ((주)선엔지니어링종합건축사사무소) ;
  • 오선교 ((주)선엔지니어링종합건축사사무소)
  • Published : 2016.05.19

Abstract

This study is aimed to analyze temperature history at each section of mat foundation concrete applying double bubble sheets. The results of the study are as follows. Firstly, the results of measuring the temperature history indicate that the lowest external temperature has been recorded at -5.6℃ for the three-day measurement period. For the central section, the result indicates that the lower, center and upper part have all secured the concrete curing temperature of 18℃ or higher. This results are believed to have resulted from excellent heat insulation performance of double bubble sheets. For the edge section between the edge form and the concrete interface, the temperature has been measured, on average, approximately 12℃ lower than the central section. However, all measured sections have indicated the temperature of 5℃ or higher. Meanwhile, an analysis has been conducted through the estimation equation of compressive strength of maturity during the curing period in order to examine the possibility of early frost damage and the aspect of securing strength. It has been confirmed that the compressive strength is higher than 50°D·D, namely, 5MPa, on the 3rd day of the aging process, which allows early frost damage to be avoided.