Direct Power Control Scheme of Improved Command Tracking Capability for PMSG MV Wind turbines

  • Kwon, Gookmin (Department of Electrical Engineering, Smart Grid Research Center, Chonbuk National University) ;
  • Suh, Yongsug (Department of Electrical Engineering, Smart Grid Research Center, Chonbuk National University)
  • Published : 2015.07.07

Abstract

This paper proposes a Direct Power Control (DPC) scheme of improved command tracking capability for Permanent Magnet Synchronous Generator (PMSG) Medium Voltage (MV) Wind Turbines. Benchmarking is performed based on a neutral point clamped three-level back-to-back type voltage source converter. It is introduced to design the DPC modeling and propose DPC scheme of a three-level NPC (3L-NPC) converter. During the fault condition in wind farms, the proposed control scheme directly controls the generated output power to the command value from the hierarchical wind farm controller. The proposed control scheme is compared with conventional control scheme as respect to loss and thermal analysis. The DPC scheme of improved command tracking capability is confirmed through PLECS simulations. Simulation result shows that proposed control scheme achieves a much shorter transient time in a step response of generated output power. The proposed control scheme makes it possible to provide a good dynamic performance for PMSG MV wind turbine to generate a high quality output power under grid fault condition.