Analysis on the Induction Effects by Separation Distance between the Power Feeding Station and the Telecommunication Cables

3점 전위강하법과 2극 측정법에 대한 접지저항 측정 결과 분석

  • Choi, Mun-hwan (ETRI(Electronics and Telecommunications Research Institute)) ;
  • Lee, Snag-mu (ETRI(Electronics and Telecommunications Research Institute)) ;
  • Cho, Pyung-dong (ETRI(Electronics and Telecommunications Research Institute))
  • Published : 2012.10.26

Abstract

RRA Notification No.2010-36 suggests the 3-point method(fall-of-Potential) using 2 auxiliary poles only as a test method of earth resistance. However this method needs to much space to install auxiliary poles so it is very difficult to measure the earth resistance in spots such as a mountain district, rocky district. So, we have analyzed the methods of 2-point method and loop resistance method in IEEE std. 81 and ITU-handbook(Earthing and Bonding) and applied these methods in test bed with 3-point method. In this paper we have compared and analyzed the earth resistance value using these 3 methods.

국립전파연구원 고시인 전기통신설비의 기술기준에 관한 표준시험방법에서는 통신 설비에 대한 접지 저항 측정 방법으로 현재 2개의 보조극을 설치하여 측정하는 3점전위강하법을 사용할 것을 권고하고 있다. 하지만 이 방법은 보조극을 설치하기 위한 공간의 확보가 어려운 지역이나 험준한 산악 지역, 암반 지역 등에서는 적용이 불가능하여 현장에서의 어려움이 예상되고 있다. 이에 IEEE와 ITU-T에서 기준이 되는 접지저항값의 만족 여부 확인만을 위하여 제시하고 있는 2극 측정법을 알아보고 테스트베드를 이용한 시험 측정을 통하여 3점전위강하법과 2극 측정법에 의해 측정된 접지저항을 비교 분석하였다.