접지시스템의 접속방식에 따른 접속요소의 열화특성 분석
Analysis of Deterioration Characteristics for Connection Factor according to Connection Method of Grounding System
-
Gil, Hyoung-Jun
(Electrical Safety Research Institute) ;
- Kim, Hyang-Kon (Electrical Safety Research Institute) ;
- Kim, Dong-Ook (Electrical Safety Research Institute) ;
- Kim, Dong-Woo (Electrical Safety Research Institute)
- 발행 : 2011.07.20
초록
This paper describes the analysis of deterioration characteristics for connection factor according to connection method of grounding system. The connection method of grounding system is specified in IEC standard. In order to analyze the deterioration characteristics for connection factor, deterioration test was carried out when the connection factor was buried in salt water and underground. The test connection factors were C-type sleeve, clamp, and exothermic welding. As a consequence, most of the connection factor was corroded, and the electrical resistance decreased after deterioration. The analytical results can be used to establish the safety of grounding system.
키워드