DC 전압이 유입변압기 절연시스템에 미치는 영향에 관한 연구

Study on the effect of DC voltage in oil-immersed transformer insulation system

  • 장효재 (현대중공업(주) 기계전기연구소) ;
  • 김용한 (현대중공업(주) 기계전기연구소) ;
  • 석복렬 (현대중공업(주) 기계전기연구소)
  • Jang, Hyo-Jae (Electro-Mechanical Research Institute, Hyundai Heavy Industries) ;
  • Kim, Yong-Han (Electro-Mechanical Research Institute, Hyundai Heavy Industries) ;
  • Seok, Bok-Yeol (Electro-Mechanical Research Institute, Hyundai Heavy Industries)
  • 발행 : 2011.07.20

초록

The HVDC transformer which is one of the main equipments for HVDC(High Voltage Direct Current) electric power transmission systems is exposed to not only AC voltage but also the inflowing DC voltage which comes from the DC-AC converter systems. Therefore, the HVDC transformer insulation system is required to withstand the electric field stress under AC, DC and DC polarity reversal conditions. However the electric field distributions under those conditions are different because the AC electric field and DC electric field are governed by permittivity and conductivity, respectively. In this study, the changes of electric potential and electric field of conventional AC transformer insulation system under DC polarity reversal test condition were analyzed by FEM(Finite Element Method). The DC electric field stress was concentrated in the solid insulators while the AC electric field stress was concentrated in the mineral oil. In addition, the electric stress under that condition which is affected by the surface charge accumulation at the interfaces between insulators was evaluated. The stress in some parts could be higher than that of AC and DC condition, during polarity reversal test. The result of this study would be helpful for the HVDC transformer insulation system design.

키워드