Scott Transformer Modeling using PSIM on the AC Substation in the Elect ric Railroad

전기철도의 교류 급전변전소에서 PSIM을 이용한 스코트변압기 모델링

  • 김성대 (서울산업대학교 철도전문대학원, 철도전기신호공학과) ;
  • 최규형 (서울산업대학교 철도전문대학원, 철도전기신호공학과)
  • Published : 2010.06.10

Abstract

In three-phase power, when the power is supplied to the single phase load, there is the unbalance of load in the three-phase power. So the scott transformer is used in the power system to supply a single phase load in three-phase power without the unbalance of loads. Especially, the scott transformer is used in the AC substation of electric railroad. Two single phase transformers are combined by T-wiring in the scott transformer. So, two single phase voltage is provided by differing $90^{\circ}$ phase in three-phase power. The selection of related equipment and correction of protective relay are not easy from characteristic of the scott transformer when shunt and ground faults occur. PSIM(Power Electronics Simulator) is optimal simulation software in field of the power electronics and provide the simple and convenient user interface. In this paper, electric model of the scott transformer is suggested and the current of the scott transformer in shunt and ground faults is analyzed. Also, the scott transformer model is demonstrated by using PSIM.

Keywords