Positioning of Partial Discharge in Insulation Oil

유중 부분방전의 위치 추정

  • 길경석 (한국해양대학교 전기전자공학부) ;
  • 박대원 (한국해양대학교 전기전자공학부) ;
  • 장운용 (한국해양대학교 전기전자공학부) ;
  • 서동환 (한국해양대학교 전기전자공학부) ;
  • 박희철 (부산교통공사 운영본부)
  • Published : 2010.06.10

Abstract

This paper described the positioning algorithm of partial discharge in insulation oil by acoustic method for the application of an on-line diagnosis in oil-immersed transformers. In the experiment, five AE sensors having the resonant frequency of 150 kHz were used, and a signal conditioner was fabricated. A needle-plane electrode system which is composed of a needle with a curvature radius of $10{\mu}m$ and a plane electrode with a diameter of 60 mm was installed to simulate partial discharges in insulation oil. From the time difference of arrival (TOA) of acoustic signal, we calculated the location of partial discharge in insulation oil. In the experiment, an algorithm of positioning of PD occurrence by the time difference of arrival was proposed. From the experimental results, the positioning error of PD calculated by three AE sensors was within 4%.