Analysis of Acoustic Noise Characteristics of Jindo-Cheju HVDC

진도-제주 HVDC 변환설비 소음특성 분석

  • Published : 2010.07.06

Abstract

HVDC converter station consists of a number of noise sources such as converter transformer, ac filter, cooling system and so on. In this paper, we analyzed the simulation results of the outdoor acoustic noise characteristics for HVDC converter station. It shows that maximum noise level in boundary of HVDC converter station exceeds regulation value. The main factors in generating maximum noise level are ac filter and converter transformer. Then we applied some soundproof countermeasure in HVDC converter station. Shielding wall is enough to reduce transformer noise level but not enough to reduce ac filter noise level. In case of ac filter, soundproof building is effective in satisfying noise level regulation in boundary of HVDC converter station. In addition, we also studied effects of season, soundproof woods, ground.

Keywords