The Optimal Design of Explosion Prevention for LPG Storage Tank

폭발방지를 고려한 LPG 저장탱크 최적설계

  • 임사환 (한국기술교육대학교 기계공학과) ;
  • 허용정 (한국기술교육대학교 메카트로닉스공학부) ;
  • 손석우 (한국기술교육대학교 메카트로닉스공학부) ;
  • 임재기 (한국기술교육대학교 메카트로닉스공학부)
  • Published : 2010.05.28

Abstract

The utilization of LPG(Liquefied Petroleum Gas) is increasing as an environmental-friendly fuel in all countries making green growth new paradigm, and use of gas is spread fast as motor fuels to decrease air pollution. Loss of lives by explosion and fire is happening every year as gas use increases, and gas accident in large scale storage property is causing serious problems socially. To minimize this problem, underground containment type storage tank is being presented as an alternative recently. In this study, to minimize explosion occurrence in underground containment type storage tank, the suitable storage tank is designed to consider explosion prevention that makes exposure surface area minimize in confined contents volume and flame to construct storage tank by the most suitable condition in the underground containment room. As a result of the design of storage tank having the most suitable condition by this research, underground containment space was minimized on diameter 3m, length 4.83m in 20 tons storage tank and its safety was improved as exposure surface area in flame decreased by 89.4%, compared with the existent storage tank.

Keywords