한국신재생에너지학회:학술대회논문집
- 2010.11a
- /
- Pages.122.2-122.2
- /
- 2010
An Experimental Study on the Thermal Performance Measurement of Standing Column Well type Borehole Heat Exchanger
스탠딩컬럼웰형(SCW) 지중열교환기의 열성능 측정에 관한 실험적 연구
- Published : 2010.11.16
Abstract
Knowledge of ground thermal properties is most important for the proper design of BHE(borehole heat exchanger) systems. The configure type, pipe size and thermal performance of the BHE is highly dependent on the ground source heatpump system-efficiency and instruction cost. Thermal response tests with mobile measurement devices were developed primarily for in-situ determination of design data for Standing Column Well apply. The main purpose has been to determine in-situ values of effective ground thermal conductivity and thermal resistance, including the effect of ground-water flow and natural convection in the boreholes. The test rig is set up on a some trailer, and contains a sub-circulation pump, a boiler, temperature sensors, flow meter and a data logger for recording the temperature and circulation fluid flow data. A constant heating power is injected into the SCW through the test rig and the resulting temperature change in the SCW is recorded. The recorded temperature data are analysed with a line-source model, which gives the effective in-situ values of rock thermal conductivity and thermal resistance of SCW.