Experimental Study on Temporary Overvoltage Characteristic of Surge Protective Devices
서지보호기의 일시과전압특성에 대한 실험적 연구
Abstract
Surge protective devices (SPD) have a special position because of the expectation that they perform an effective protective function against various kinds of surges. However, there exists a misconception that the SPD satisfying lower measured limiting voltage (MLV) should also protect equipment against temporary overvoltages (TOVs) as well. This paper inspects various types of MOV based SPDs and carry out experiments on the side effects of the low MLV characteristics. The experiment results show that a low MLV could cause a higher TOV-induced SPD failure rate in the field.