접지임피던스 측정에 관한 전류보조전극 거리 및 주파수의 영향 분석

Analysis for Ground Impedance Measurement Influenced by Distance of Current Probe and Frequency

  • 발행 : 2009.05.07

초록

This paper describes the analysis for ground impedance measurement influenced by distance of current probe and frequency using the fall-of-potential method and the testing techniques to minimize the measuring errors are proposed. The fall-of-potential method is theoretically based on the potential and current measuring principle and the measuring error is primarily caused by the position of auxiliary probes. In order to analyze the effects of ground impedance due to the distance of the current probe and frequency, ground impedances were measured in case that the distance of current probe was located from 5[m] to 20[m] and the measuring frequency was ranged in 55[Hz], 128[Hz], 342[Hz], and 513[Hz]. The results could be help to determine the position of current probe when the ground impedance was measured at grounding system.