한국조명전기설비학회:학술대회논문집 (Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference)
- 한국조명전기설비학회 2009년도 춘계학술대회 논문집
- /
- Pages.289-292
- /
- 2009
접지임피던스 측정에 관한 전류보조전극 거리 및 주파수의 영향 분석
Analysis for Ground Impedance Measurement Influenced by Distance of Current Probe and Frequency
- 발행 : 2009.05.07
초록
This paper describes the analysis for ground impedance measurement influenced by distance of current probe and frequency using the fall-of-potential method and the testing techniques to minimize the measuring errors are proposed. The fall-of-potential method is theoretically based on the potential and current measuring principle and the measuring error is primarily caused by the position of auxiliary probes. In order to analyze the effects of ground impedance due to the distance of the current probe and frequency, ground impedances were measured in case that the distance of current probe was located from 5[m] to 20[m] and the measuring frequency was ranged in 55[Hz], 128[Hz], 342[Hz], and 513[Hz]. The results could be help to determine the position of current probe when the ground impedance was measured at grounding system.