Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference (한국조명전기설비학회:학술대회논문집)
- 2009.10a
- /
- Pages.211-213
- /
- 2009
The Study of Cable Fault Case and the Fault Management System of Electrical Facilities for private use
자외선 영상 이미지 비교를 통한 22.9kV 특고압 설비의 상태진단 연구
- Published : 2009.10.09
Abstract
This paper was studied about the ultra-violet rays(UV) image area and discharge quantity of 22.9kV class polymer insulator using UV camera. The UV image area was begun to observe to 60kV that is about 40% of breakdown voltage of polymer insulator and the area was increased by applied voltage. Also, the discharge quantity was increased at 60kV sharply. If the intensity of breakdown passes over about 40% we can know that need the check on the electrical facility.
Keywords