전력케이블의 절연결함에 따른 부분방전 특성분석

Analysis of PD Characteristics by Types of Insulation Defects in Power Cables

  • 최재성 (한국해양대학교 전기전자공학부) ;
  • 박찬용 (한국해양대학교 전기전자공학부) ;
  • 김선재 (한국해양대학교 전기전자공학부) ;
  • 한주섭 (한국해양대학교 산업기술연구소) ;
  • 길경석 (한국해양대학교 전기전자공학부)
  • 발행 : 2009.05.21

초록

This paper described partial discharge(PD) patterns depending on types of insulation defects in CNCO-W cable(Concentric Neutral Closs-linked Polyethylene Insulated Polyolefin-Water Proof Sheathed Power Cable). The PD measurement system consists of a coupling network, a detection impedance, and a low noise amplifier. A 16 bit, 250 MS/s data acquisition system was used to analyze PD patterns. To simulate insulation defects in a power cable, a needle with the curvature radius of $10{\mu}m$ was inserted into the insulation part. We measured phase ($\Phi$), magnitude (q), and counts (n) of PD pulse for the defects, and classified PD patterns using the PRPD (phase Resolved Partial Discharge) method. From the analysis of acquired PD signals, we could find that a unique PD pattern is formed according to the types of defect.

키워드