AC Breakdown Voltage Characteristics of $SF_6/CF_4$ and (E/P)crit in quasi-uniform Field

준평등전계에서 $SF_6/CF_4$ 혼합가스의 절연 파괴 전압 및 임계전계 특성

  • Published : 2009.07.14

Abstract

$SF_6$ is the most commonly used insulating gas in electrical systems. But In these days $SF_6$ mixtures and alternative gas has been studied because of global warming. so although many studies have been carried out about binary gas mixtures with $SF_6$, few studies were presented about breakdown characteristics of $SF_6/CF_4$ mixtures. At present study the breakdown characteristics of $SF_6/CF_4$ mixtures in quasi-uniform field was performed. This experiments were carried out under AC voltages. The rod-rod electrode was used with 5 mm gap distance. The mixture of $SF_6/CF_4$ containing 20%,50%,70% of $SF_6$ were compared with pure $SF_6$ and $CF_4$ gas and gas pressure ranged from 0.1 to 0.5 MPa. The show that the breakdown voltages of gas were linearly increased according to the pressure in quasi-uniform field. For breakdown vlotage values of $(E/P)_{crit}$ are important. Because If values of (E/P) is a little more than $(E/P)_{crit}$, electrons rapidly increase and streamer discharge gernerates. Through this experiments values of $(E/P)_{crit}$ are found to vary with the ratio of $SF_6/CF_4$ mixture according to the following relationship. $V_b=(E/P)_{crit}{\cdot}p{\cdot}d$