4.16kV 전동기 고정자 권선의 절연열화 특성

Characteristics of Insulation Aging in 4.16kV Motor Stator Windings

  • 발행 : 2009.07.14

초록

Nondestructive tests were performed on two 4.16kV motors. Epoxy-mica coupler(80pF) was connected to 4.16 kV motor stator windings. The voltage applied to the stator windings was 2.4 kV, 3.0kV, 3.5kV and 4.16kV, respectively. Digital partial discharge detector(PDD) and turbine generator analyzer(TGA) were used to measure partial discharge(PD) activity. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). The PD levels in pC were measured with PDD. PD patterns of stator windings were indicated the internal discharge. PD patterns are consistent with the result of measurement using PDD and TGA.