Development of Three-Phase Line-Interactive Dynamic Voltage Restorer with Hybrid Detection Method

Hybrid 검출방식을 적용한 삼상 선로 응동형 DVR(Dynamic Voltage Restorer)

  • Published : 2009.07.14

Abstract

This paper describes the development of a three-phase Line-Interactive DVR(Dynamic Voltage Restorer), which is applied to Hybrid detection method and super-capacitor. The operational feasibility was verified through computer simulations with PSCAD/EMTDC software, and experimental will be work with 3kVA prototype. The developed system can compensates the input voltage sag and interruption within 2ms, in which the maximum allowable sensitive load, such as computer, communication equipment, automation equipment, and medical equipment. The developed system has a simple structure to be easily implemented with commercially available components and to be highly reliable in operation.

Keywords