Control System of 600kW EBOP for Molten Carbonate Fuel Cell Generation System

600kW급 용융탄산염 연료전지 발전시스템용 EBOP 제어시스템

  • Published : 2008.06.30

Abstract

An electrical balance of plant(EBOP) of a 600kW molten carbonate fuelcell (MCFC) has to transit from grid-connected(GC) mode to grid-independent(GI) mode when a grid is in a fault conditions. A minimum transition time is limited by four cycle for a 600kW MCFC to ride through a grid fault. In this paper, we propose a control algorithm of a 600kW EBOP for a MCFC system. The EBOP has three operation modes, i.e., GC mode, GI mode, and grid-synchronized(GS) mode. The EBOP controls output currents in a GC mode and regulates output voltages in GI or GS mode. GS mode is defined as an interface between GC mode and GI mode to make a mode transition smooth, i.e., limitation of inrush currents, regulation of output voltages within ANSI standard. Simulations and experiments carried out to verify the effectiveness of the proposed control algorithm.

Keywords