Effects of Auxiliary Probe on Low Frequency Ground Impedance Measurement

저주파 접지임피던스 측정에 미치는 보조전극의 영향

  • Published : 2008.10.17

Abstract

In this paper, the effects of the position and the angle of the auxiliary probes on the measurements of the low frequency ground impedance with the fall-of-potential method are described iud the testing techniques to minimize the measuring errors are proposed. The fall-of-pot ential method is theoretically based on the potential and current measuring principle and the measuring error is primarily caused by the position and angle of auxiliary probes. In order to analyze the characteristics of ground impedance due to the location of the potential probe, ground impedances were measured in case that the distance of current probe was fixed at 50[m] and the distance of potential probe was located from 10[m] to 50[m]. Also, the potential robe was located at 30[$^{\circ}$], 40[$^{\circ}$], 60[$^{\circ}$], 90[$^{\circ}$], and 180[$^{\circ}$]. The results could be help to determine the location of potential probe when the ground impedance was measured at grounding system.