한국조명전기설비학회:학술대회논문집 (Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference)
- 한국조명전기설비학회 2008년도 추계학술대회 논문집
- /
- Pages.301-306
- /
- 2008
몰드변압기에서 부분방전 검출방법의 비교분석
Comparison Analysis of Partial Discharge Detection Methods in Cast Resin Dry Type Transformers
- 발행 : 2008.10.17
초록
Various sensors such as capacitive probe, high frequency current transformer (HFCT), and acoustic emission (AE) probe were applied to a cast resin dry type transformer for partial discharge detection. We designed and fabricated a wideband low-noise amplifier having a gain of 40[dB]. From the experiment which was carried out in the same transformer, the sensitivities were 7.16[mV/pC] for capacitive probe, 3.8[mV/pC] for HFCT, and 17.9[mV/pC] for AE probe.
키워드